Analisis Keandalan Sistem Jaringan Distribusi Tegangan Menengah 20KV pada Penyulang an Nur PT. Pln UP3 Surabaya Barat dengan Metode Realibility Index Assesment ( Ria)
Abstract
The main components of an electric power system do not escape the three
components covering the generating system, transmission network and
distribution system. These three components do not escape the need for a security
or institution that handles or oversees the flow of electrical energy in an area. PT
PLN Persero itself is a state-owned enterprise that oversees and oversees the
distribution of electrical energy from the process of generating electricity to
distributing electricity to consumers throughout Indonesia. which certainly
requires a large enough source of electrical energy supply. So that a research on
the reliability of the 20 KV medium voltage distribution system network is
focused on at PT PLN UP3 West Surabaya which has one of the feeders, namely
the An Nur feeder.
This study discusses the reliability of the 20 KV medium voltage
distribution system network by comparison with SPLN 59 of 1985. The method
used is the Reliability Index Assessment method where supporting data is needed
in the research obtained from PT PLN UP3 West Surabaya including data on An
Nur feeder number of subscribers , power capacity, as well as the single line
diagram so that in data processing it is hoped that the output reliability index of
the distribution system SAIDI, SAIFI, CAIDI will be obtained. Then based on the
single line diagram of the An Nur feeder, a simulation will be modeled on ETAP
12.6.0.
The results of this study for the reliability value of the conventional
calculation system obtained a SAIFI value of 0.062798 disturbances/year, SAIDI
with a value of 0.188395 hours/year, and CAIDI of 3 disturbances/hour/year. In