OPTIMASI PENEMPATAN KAPASITOR PADA SISTEM DISTRIBUSI LISTRIK DENGAN METODE CLONAL SELECTION (STUDI KASUS DI PENYULANG WATU ULO JEMBER)
Abstract
Like the inductive load increase, reactive power which is put inside the network
will be bigger and it will cause voltage drop at the end of line also increase
network losses. Various attempts have been made to lessen the voltage drop and
network losses. One way to do is installing capacitor for reactive power
compensation. The location of capacitors on distribution network system that has
various bus loads that need to be optimized. The addition of capacitors Clonal
Selection used as method to determine the location of capacitors. The results of
Clonal Selection Method that used at Watu Ulo feeders in PT. PLN APJ Jember
are the location of capacitors that has installed are at Trafo Bus GE197 and GE
138, approximately 400 kVar. After the installment of capacitors, voltage around
the end of feeders increase into 1.16% and also decrease the network losses for
Rp. 279.936.000,00/year.