dc.description | Jurnal Pembelajaran Fisika, Vol 6 No. 1, Maret 2017, hal 83-91 | en_US |
dc.description.abstract | The current study is based on the needs of human life that cannot be
separated from the role of electricity. This is why the demand for electricity is
getting increased, so it requires the construction of transmission channels, one of
them is SUTT. Without realizing it, the channel emits magnetic field. The exposure
to magnetic field generated by SUTT has extremely low frequency since the rate
commonly used in Indonesia is 50 Hz. The purpose of the current study was to find
out the distribution pattern of magnetic field radiation intensity below SUTT 150 kV
and the influence of roof types to the decrease of ELF magnetic field intensity by
SUTT 150 kV. The study design was field experiment using measuring devices of
magnetic field with EMF-827. The results confirmed that the area under the phase
wires had the greatest magnetic field intensity, that was almost 70 times bigger than
that of the natural magnetic field intensity. Based on the data collection, the use of
roof barrier did not effect to the decrease of the magnetic field intensity because the
decrease had segnificantly occured at farther distance from the phase wires without
using roof barriers. All the results of magnetic field intensity measurements was still
below the limit allowed by WHO. The results of the current study can be used as
new understanding for Indonesians, especially those who still live under the
transmission line. | en_US |