dc.description.abstract | Insulating oil pick the many standards for testing to test the insulating oil insulation
either new or have been used (maintenance), such as breakdown voltage, dielectric
losses, relative permittivity, and testing by the method of DGA (Dissolved Gas
Analysis). DGA is a method of testing performed to test the insulating oil state by
taking samples from the unit transformer insulating oil to determine the types of gas
dissolved in transformer insulating oil. DGA is one step preventive maintenance but
object insulating oil which is done only consider the results TDCG (Total Dissolved
Combustible Gas) without considering other types of gas contained in transformer
insulating oil such as hydrogen gas, methane, ethane, ethylene, acetylene, carbon
dioxide, and carbon monoxide . Insulating oil situation will be resolved by using
Fuzzy Logic. Fuzzy logic analysis performed for insulating oil state would be more
accurate than if done by simply analyzing the gas concentration TDCG. | en_US |
dc.language.iso | other | en_US |
dc.relation.ispartofseries | 071910201083; | |
dc.subject | transformer oil, insulation, preventive maintenance, DGA fuzzy logic, TDCG, gas. | en_US |
dc.title | ANALISIS KEADAAN MINYAK ISOLASI TRANSFORMATOR DAYA 150 kV MENGGUNAKAN METODE DISSOLVED GAS ANALYSIS (DGA) DAN FUZZY LOGIC PADA GARDU INDUK WILAYAH SIDOARJO | en_US |